Range: 49.2” (1.25m)
Accuracy: 0.125” (3mm)
Resolution: 0.019” (0.5mm)
Dead band: 2” (5cm)
Beam width: 2” (5cm)
Configuration: WebCal® PC Windows®, USB 2.0
Memory: Non-volatile
Supply voltage: 12-24 VAC / VDC
Consumption: 0.5W
Contact type: (4) SPST relays, 1A
Contact fail-safe: Power loss: Hold last, Power on: Open, close or hold last
Hysteresis: Selectable
Process temp.: F: 20° to 140°, C: -7° to 60°
Temp. comp.: Automatic
Ambient temp.: F: -31° to 140°, C: -35° to 60°
Pressure: MWP 30 PSI (2 bar)
Enclosure rating: Type 6P, encapsulated, corrosion resistant & submersible
Encl. material: Polycarbonate
Strain relief mat.: Santoprene
Trans. material: PVDF
Cable jacket mat.: Polyurethane
Cable type: 9-conductor, shielded
Cable length: 48” (1.2m)
Process mount: 1” NPT (1” G)
Mount gasket: Viton®
Classification: General purpose
Compliance: CE, RoHS
Approvals: cFMus
CONFIGURATION
WebCal® software is a PC utility program that enables users to easily configure and test compatible Flowline level sensors to their measurement and control requirements.
FEATURES
- Level detection, switch and control functions up to 49.2” (1.25m)
- Configuration is fast and easy via WebCal software and USB adapter
- Narrow 2” beam width and short 2” dead band optimized for small tanks
- Four programmable relays for switch, pump or valve control and fail-safety
- 1 pump or valve with 3 alarms
- 2 pumps lead-lag with 2 alarms
- 2 pumps duplexing with 2 alarms
- 4 independent switch point alarms
- PVDF transducer and 6P polycarbonate enclosure for corrosive liquids
- Automatic temperature compensation for accurate measurement