Output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
formula for output voltage Vin - approx. 0.5 V
output voltage
● at output 1 at DC rated value 24 V
product function output voltage adjustable No
display version for normal operation Green LED for "both Input voltages > switching threshold"; red LED: for "at
least one input voltage < switching threshold"
type of signal at output Isolated relay contact (changeover contacts, rating 8 A/240 V AC, 24 V DC):
Signals OK if both input voltages > switching threshold, setting range of
threshold 20 ... 25 V
output current
● rated value 40 A
● rated range 40 A; max. aggregate current 40 A; +60 ... +70 °C: derating 3%/K
Efficiency
efficiency in percent 96.6 %
power loss [W]
● at rated output voltage for rated value of the output
current typical
34 W
● during no-load operation maximum 1.5 W
Safety
galvanic isolation yes, SELV acc. to EN 60950-1 (relay contact)
operating resource protection class Class III
protection class IP IP20
Approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● cCSAus, Class 1, Division 2 No
● ATEX No
certificate of suitability
● IECEx No
● NEC Class 2 No