Product Overview
| Suitable Applications | Intercom/Audio Systems |
Construction Details
Conductor
| Element | No. of Elements | Size | Stranding | Material |
| Conductor(s) | 2 | 18 AWG | 7x26 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
| Conductor(s) | PVC - Polyvinyl Chloride | 0.009 in (0.23 mm) | 0.063 in (1.6 mm) | Black, Red |
Outer Jacket
| Material | Nom. Thickness | Nom. Diameter | Ripcord | |
| PVC - Polyvinyl Chloride | 0.015 in (0.38 mm) | 0.154 in (3.91 mm) | Yes | |
| Overall Cable Diameter (Nominal) | 0.154 in (3.91 mm) | |||
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Max. Current |
| Conductor(s) | 6.5 Ohm/1000ft | 34 pF/ft (110 pF/m) | 14 Amps per conductor @ 25°C |
Voltage
| UL Voltage Rating |
| 300 V |
Mechanical Characteristics
Temperature
| UL Temperature | Operating |
| 75°C | 0°C to +75°C |
Bend Radius
| Stationary Min. | Installation Min. |
| 1.5 in (38 mm) | 1.5 in (38 mm) |
| Max. Pull Tension | 45 lbs (20 kg) |
| Bulk Cable Weight | 17 lbs/1000ft |
Standards and Compliance
| Environmental Suitability | Indoor - Plenum, Indoor |
| Flammability / Reaction to Fire | NFPA 262, UL 910 (Plenum), FT6, IEC 60332-1-2 |
| CPR Compliance | CPR Euroclass: Eca |
| NEC / UL Compliance | Article 800, CMP |
| CEC / C(UL) Compliance | CMP |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK Regulation Compliance | UKCA Mark |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Non-Plenum Number | 5300UE |