Control circuit/ Control
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value 110 V
● at 60 Hz rated value 120 V
Control supply voltage frequency
● 1 rated value 50 Hz
● 2 rated value 60 Hz
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz 0.8 ... 1.1
● at 60 Hz 0.8 ... 1.1
Apparent pick-up power of magnet coil at AC 69 V·A
Inductive power factor with closing power of the coil 0.76
Apparent holding power of magnet coil at AC 7.5 V·A
Inductive power factor with the holding power of the
coil
0.28
Auxiliary circuit
Number of NC contacts for auxiliary contacts
● instantaneous contact 0
Number of NO contacts for auxiliary contacts
● instantaneous contact 0
Operating current at AC-12 maximum 10 A
Operating current at AC-15
● at 230 V rated value 6 A
● at 400 V rated value 3 A
Operating current at DC-12
● at 60 V rated value 6 A
● at 110 V rated value 3 A
● at 220 V rated value 1 A
Operating current at DC-13
● at 24 V rated value 10 A
● at 60 V rated value 2 A
● at 110 V rated value 1 A
● at 220 V rated value 0.3 A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)