New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A

New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A

Regular price $99.99 Save $-99.99
/

Only 13 items in stock!
New Lederle Hermetic ROMe 262000011 Rotation Monitor 3AC 380-690V 40-80Hz 5A

New product pulled from bulk OEM packaging.  Each order is for 1 piece.

Fast US Shipping

30-day Warranty.

MFR Details : 


·         According to DIN EN 60255

• Detection of incorrect phase sequence

• No separately auxiliary voltage necessary

• Nominal voltage range 3 AC 380 ... 690 V

• Suitable for frequency converter (f 40 ... 80 Hz)

• Output: NC contact (open at incorrect phase sequence)

• Extended temperature range

• ROMi: potted module with stranded wire connection

suitable for mounting in terminal box

• Width ROMe: 35 mm (1.4 in)


 Applications : To avoid wrong sense of rotation on 3-phase motors

5. Technical Data

Input (L1-L2-L3) (ROMi: stranded wire red-blue-grey)

Nominal voltage UN: 3 AC 380 ... 690 V

Voltage range: 0.85 ... 1.1 UN (3 AC 320 ... 760 V)

Nominal consumption: approx. 3 VA

Frequency range: 40 ... 80 Hz (main frequency);

suitable for frequency converter

Output (7-8) (ROMi: stranded wire yellow-green)

Contact: 1 NC contact

Reaction time: After connection of all 3 phases with

wrong phase sequence until NC

contact opens: approx. 100 ms

Thermal current Ith

ROMi: 2 A

ROMe: 5 A

Switching capacity ROMi

acc. AC 15: 1 A / AC 230 V IEC/EN 60 947-5-1

acc. DC 13: 1 A / DC 24 V IEC/EN 60 947-5-1

Switching capacity ROMe

acc. AC 15: 2 A / AC 230 V IEC/EN 60 947-5-1

acc. DC 13: 2 A / DC 24 V IEC/EN 60 947-5-1

Electrical life time: 1.5 x 105 switching cycles

Short circuit strength

max. fuse rating

ROMi: 2 A gL IEC/EN 60 947-5-1

ROMe: 4 A gL IEC/EN 60 947-5-1